Specifications |
Accuracy |
Parameter |
Range |
Resolution |
Intrinsic Accuracy at Reference Conditions (% of Reading + % of Full Scale) |
Voltage |
1000 V |
0.1 V |
± (0.2 % + 0.01 %) |
Current: Direct input |
iFlex1500-12 |
150 A |
0.1 A |
± (1 % + 0.02 %) |
1500 A |
1 A |
iFlex3000-24 |
300 A |
1 A |
± (1 % + 0.02 %) |
3000 A |
10 A |
iFlex6000-36 |
600 A |
1 A |
± (1.5 % + 0.03 %) |
6000 A |
10 A |
i40s-EL clamp |
4 A |
1 mA |
± (0.7 % + 0.02 %) |
40 A |
10 mA |
Frequency |
42.5 Hz to 69 Hz |
0.01 Hz |
± (0.1 %) |
Auxillary input |
± 10 V dc |
0.1 mV |
± (0.2 % + 0.02 %) |
Voltage min/max |
1000 V |
0.1 V |
± (1 % + 0.1 %) |
Current min/max |
defined by accessory |
defined by accessory |
± (5 % + 0.2 %) |
Cosφ/DPF |
0 <= Cosφ <=1 |
0.01 |
± 0.025 |
Power factor |
0 <= PF <=1 |
0.01 |
± 0.025 |
THD on voltage |
1000 % |
0.1 % |
± (2.5 % ± 0.05) |
THD on current |
1000 % |
0.1 % |
± (2.5 % ± 0.05) |
Intrinsic Uncertainty ± (% of reading + % of range)1 |
Parameter |
Influence quantity |
iFlex1500-12 |
iFlex3000-24 |
iFlex6000-36 |
i40S-EL |
150A/1500A |
300A/3000A |
600/6000A |
4A/40A |
Active power P |
PF ≥ 0.99 |
1.2 % + 0.005 % |
1.2 % + 0.0075 % |
1.7 % + 0.0075 % |
1.2 % + 0.005 % |
0.5 < PF < 0.99 |
1.2 % + 7 x (1-PF) +0.005 % |
1.2 % + 7 x (1-PF) + 0.0075 % |
1.7 % + 7 x (1-PF) + 0.0075 % |
1.2 % + 10 x (1-PF) + 0.005 % |
Apparent power S, S fund. |
0 ≤ PF ≤ 1 |
1.2 % + 0.005 % |
1.2 % + 0.0075 % |
1.7 % + 0.0075 % |
1.2 % + 0.005% |
Reactive power N, Q fund. |
0 ≤ PF ≤ 1 |
2.5 % of measured apparent power |
Additional uncertainty in % of range1 |
U >250 V |
0.015 % |
0.0225 % |
0.0225 % |
0.015 % |
1Range = 1000 V x Irange
Reference conditions:
Environmental: 23 °C ± 5 °C, instrument operating for at least 30 minutes, no external electrical/magnetic field, RH <65 %
Input conditions: Cosφ/PF=1, Sinusoidal signal f=50 Hz/60 Hz, power supply 120 V/230 V ±10 %
Current and power specifications: Input voltage 1 ph: 120 V/230 V or 3 ph wye/delta: 230 V/400 V
Input current: I > 10 % of Irange
Primary conductor of clamps or Rogowski coil in center position
Temperature coefficient: Add 0.1 x specified accuracy for each degree C above 28 °C or below 18 °C |
Electrical Specifications |
Power Supply |
Voltage range |
100 V to 500 V using safety plug input when powering from the measurement circuit |
100 V to 240 V using standard power cord (IEC 60320 C7) |
Power consumption |
Maximum 50 VA (max. 15 VA when powered using IEC 60320 input) |
Efficiency |
≥ 68.2 % (in accordance with energy efficiency regulations) |
Maximum no-load consumption |
< 0.3 W only when powered using IEC 60320 input |
Mains power frequency |
50/60 Hz ± 15 % |
Battery |
Li-ion 3.7 V, 9.25 Wh, customer-replaceable |
On-battery runtime |
Four hours in standard operating mode, up to 5.5 hours in power saving mode |
Charging time |
< 6 hours |
Data Acquisition |
Resolution |
16-bit synchronous sampling |
Sampling frequency |
5120 Hz |
Input signal frequency |
50/60 Hz (42.5 to 69 Hz) |
Circuit types |
1-φ, 1-φ IT, Split phase, 3-φ delta, 3-φ wye, 3-φ wye IT, 3-φ wye balanced, 3-φ
Aron/Blondel (2-element delta), 3-φ delta open leg, Currents only (load studies) |
THD |
THD for voltage and current is calculated using 25 harmonics |
Averaging period |
User selectable |
1 sec, 5 sec, 10 sec, 30 sec, 1 min, 5 min, 10 min, 15 min, 30 min |
Demand interval |
User selectable |
5 min, 10 min, 15 min, 20 min, 30 min |
Data storage |
Internal flash memory (not user replaceable) |
Memory size |
Typical 20 logging sessions of 10 weeks with 10-minute intervals¹ |
Logging period |
Averaging period
Recommended |
20 sessions |
1 session |
1 second |
3 hours |
2.5 days |
5 seconds |
15 hours |
12 days |
10 seconds |
28 hours |
24 days |
30 seconds |
3.5 days |
10 weeks |
1 minute |
7 days |
20 weeks |
5 minutes |
5 weeks |
2 years |
10 minutes |
10 weeks |
> 2 years |
15 minutes |
3.5 months |
> 2 years |
30 minutes |
7 months |
> 2 years¹ |
Interfaces |
USB-A |
File transfer via USB flash drive, firmware updates
Max. current: 120 mA |
USB-mini |
Data download device to PC |
Extension port |
Accessories |
Voltage Inputs |
Number of inputs |
4 (3 phases and neutral) |
Maximum input voltage |
1000 Vrms, CF 1.7 |
Input impedance |
10 MΩ |
Bandwidth (-3 dB) |
2.5 kHz |
Scaling |
1:1, 10:1, 100:1, 1000:1 and variable |
Measurement category |
1000 V CAT III/600 V CAT IV |
Current Inputs |
Number of inputs |
3, mode selected automatically for attached sensor |
Input voltage |
Clamp input: 500 mVrms/50 mVrms; CF 2.8 |
Rogowski coil input |
150 mVrms / 15 mVrms at 50 Hz, 180 mVrms / 18 mVrms at 60 Hz; CF 4; all at nominal probe range |
Range |
1 A to 150 A/10 A to 1500 A with thin iFlex flexible current probe, 12 inches |
3 A to 300 A/30 A to 3000 A with thin iFlex flexible current probe, 24 inches |
6 A to 600 A/60 A to 6000 A with thin iFlex flexible current probe, 36 inches |
40 mA to 4 A/0.4 A to 40 A with 40 A clamp i40s-EL |
Bandwidth (-3 dB) |
1.5 kHz |
Scaling |
1:1 and variable |
Auxiliary Inputs |
Number of inputs |
2 |
Input range |
0 to ± 10 V dc, 1reading/s |
Scale factor (available 2014) |
Format: kx + d user configurable |
Displayed units (available 2014) |
User configurable (7 characters, for example, °C, psi, or m/s) |
- The number of possible logging sessions and logging period depends on user requirements.
|
Environmental Specifications |
Operating temperature |
-10 °C to +50 °C (14 °F to 122 °F) |
Storage temperature |
-20 °C to +60 °C (−4 °F to 140 °F) |
Operating humidity |
10 °C to 30 °C (50 °F to 86 °F) max. 95 % RH |
30 °C to 40 °C (86 °F to 104 °F) max. 75 % RH |
40 °C to 50 °C (104 °F to 122 °F) max. 45 % RH |
Operating altitude |
2000 m (up to 4000 m derate to 1000 V CAT II/600 V CAT III/300 V CAT IV) |
Storage altitude |
12,000m |
Enclosure |
IP50 in accordance with EN60529 |
Vibration |
MIL 28800E, Type 3, Class III, Style B |
Safety |
IEC 61010-1: Overvoltage CAT IV, Measurement 1000 V CAT III / 600 V CAT IV, Pollution Degree 2 |
EMI, RFI, EMC |
EN 61326-1: Industrial |
Electromagnetic compatibility |
Applies to use in Korea only. Class A equipment (industrial broadcasting and communication equipment) |
Radio frequency emissions |
IEC CISPR 11: Group 1, Class A |
Temperature coefficient |
0.1 x accuracy specification/°C |
General Specifications |
Color LCD display |
4.3-inch active matrix TFT, 480 pixels x 272 pixels, resistive touch panel |
Warranty |
1730 and power supply |
Two-years (battery not included) |
Accessories |
One-year |
Calibration cycle |
Two-years |
Dimensions |
1730 |
19.8 cm x 16.7 cm x 5.5 cm (7.8 in x 6.6 in x 2.2 in) |
Power supply |
13.0 cm x 13.0 cm x 4.5 cm (5.1 in x 5.1 in x 1.8 in) |
1730 with power supply attached |
19.8 cm x 16.7 cm x 9 cm
(7.8 in x 6.6 in x 3.5 in) |
Weight |
1730 |
1.1 kg (2.5 lb) |
Power supply |
400 g (0.9 lb) |
External protection |
Holster, Kensington lock slot |
1500-12 iFlex Flexible Current Probe
Specifications |
Measuring range |
1 to 150 A ac / 10 to 1500 A ac |
Nondestructive current |
100 kA (50/60 Hz) |
Intrinsic error at reference condition* |
± 0.7 % of reading |
Accuracy 1730 + iFlex |
± (1 % of reading + 0.02 % of range) |
Temperature coefficient over operating temperature range |
0.05 % of reading/°C 0.09 % of reading/°F |
Working voltage |
1000 V CAT III, 600 V CAT IV |
Probe cable length |
305 mm (12 in) |
Probe cable diameter |
7.5 mm (0.3 in) |
Minimum bending radius |
38 mm (1.5 in) |
Output cable length |
2 m (6.6 ft) |
Weight |
115 g |
Transducer cable material |
TPR |
Coupling material |
POM + ABS/PC |
Output cable |
TPR/PVC |
Operating temperature |
-20 °C to +70 °C (-4 °F to 158 °F) temperature of conductor under test shall not exceed 80 °C (176°F) |
Temperature, non-operating |
-40 °C to +80 °C (-40 °F to 176 °F) |
Relative humidity, operating |
15 % to 85 % non-condensing |
IP rating |
IEC 60529:IP50 |
Warranty |
One-year |
*Reference condition:
- Environmental: 23 °C ± 5 °C, no external electrical/magnetic field, RH 65 %
- Primary conductor in center position
|
|
|
|
|
Reviews